Aggremax SF6 Gas Fully Insulated High Voltage AC Metal Ring Main Unit
+
  • Aggremax SF6 Gas Fully Insulated High Voltage AC Metal Ring Main Unit

Aggremax SF6 Gas Fully Insulated High Voltage AC Metal Ring Main Unit

Hengxuan Electric is committed to providing customers with research and development, production, sales, and installation (repair, testing) of complete electrical equipment and comprehensive supporting services.

Keywords: High and Low Voltage Complete Sets | Box-type Substation | Power Transformer

  • Description
  • Technical Specifications
  • This compact ring main unit encloses all live parts within an IP67-rated stainless steel enclosure. The entire switchgear is unaffected by external environmental conditions, ensuring operational reliability and personal safety, while achieving maintenance-free operation. By selecting expandable busbars, any combination can be realized to achieve full modularity. The expandable busbars are fully insulated and shielded, ensuring high reliability and safety. The Aggremax series switches also offer factory-automated solutions, forming the concept of intelligent switching and minimizing on-site installation and commissioning workload.

    Aggremax is available in standard configurations of 2, 3, 4, 5, or 6 ways, with additional equipment added according to customer requirements. Due to its combination of full and half modules and its own expandability, Aggremax offers exceptional flexibility.

    Product Features:

    Switches are mutually interlocked, switch position indicators are clear, and come standard with live indication functions to ensure safety.

    Reliable: Pressure relief channels are designed to prevent arc faults, tested with a 20kA internal arc fault test.

    Stable: Programmed design, standardized process control, and modular combinations ensure stable quality.

    Fully insulated, fully enclosed, maintenance-free:

    All high-voltage live parts are completely enclosed within the SF6 tank, with a protection rating of IP67. The entire switchgear is unaffected by external environmental conditions, allowing arbitrary combinations and unlimited expansion.

    Can be used in separated compartments or achieve multi-way units sharing a compartment, freely combining various module units to meet different customer needs.

    Modules can be flexibly expanded on-site, easily building various medium-voltage substations with different requirements. Modular design allows free expansion and combination.

    Wide applicability:

    User distribution rooms, outdoor switching stations, box-type substations, wind power generation, hydroelectric power generation.

    Basements, damp and condensation conditions, plateau climates, low temperatures, large temperature differences.

    Intelligent:

    Can provide intelligent distribution network systems with supporting functions such as protection, remote control, monitoring, and fault handling.

  • Parameter Unit L Module T Module V Module   CB Module  
    Load Switch Combined Electrical Apparatus Vacuum Circuit Breaker Isolating/Grounding Switch Vacuum Circuit Breaker Isolating/Grounding Switch
    Rated Voltage kV 12/24 12/24 12/24 12/24 12/24 12/24
    Power Frequency Withstand Voltage kV 42/65 42/65 42/65 42/65 42/65 42/65
    Lightning Impulse Withstand Voltage kV 75/125 75/125 75/125 75/125 75/125 75/125
    Rated Current A 630/630 Note 1) 630/630   1250/800  
    Breaking Capacity
    Closed Loop Breaking Current A 630/630      
    Cable Charging Breaking Current A 135/135      
    5% Rated Active Load Breaking Current A 31.5/-      
    Ground Fault Breaking Current A 200/150      
    Cable Charging Breaking Current During Ground Fault A 115/87      
    Short Circuit Breaking Current kA   Note 2) 20/16 or 25/20   25(20) Note 3)  
    Closing Capacity kA 63/52.5 Note 2) 50/40 or 63/50 50/40 63(50) Note 3) 63/50
    Short-time Withstand Current 2 seconds kA 25/-  25    
    Short-time Withstand Current 3 seconds kA -/21   20/16 20/16 25(20) Note 3) 25/20
    Mechanical Life Times 5000 3000 5000 2000 10000 2000 

    Note 1): Depends on the current rating of the fuse.

    Note 2): Limited by high-voltage fuse.

    Note 3): The number in parentheses is the parameter of the 800A cabinet type in the 24KV system.

    Standards Followed:

    IEC 62271-100, IEC 62271-102, IEC 62271-103, IEC 62271-200, IEC 62271-105, IEC 62271-1

    GB/T 11022-2011, GB 3906-2006, GB 1985-2004, GB 16926, GB 3804-2004, GB 1984-2003, GB 3309-89

Application Industries

Message

If you have any needs, please feel free to contact us.

Submit Now