Low voltage AC withdrawable complete set

产品系列

Low voltage AC withdrawable complete set
GCS

GCS

GCS

  • Description
  • Data Sheet
  • Product Introduction

    The GCS is suitable for power plants, transformer substations, petrochemical sectors, factories, mining, hotels and high buildings, as the LV power distribution systems, power distribution and motor control centers, electrical capacitance compensation control centers and the capacitance switching, distribution and control of the capacitance compensation.

    It can meet the special needs of the computer interfaces in the low-voltage power control centers and the motor control centers of the power plants and petrochemical industries with large single machine capacity.

    According to the requirements of customers, the design is to meet the needs of capacity increase, computer interface, power centralized control, easy installation and maintenance and shortening the accident disposal time. The system has the good functions of safety, economy and reasonableness, and it is a low-voltage draw out switchgear and charaterized by its high capacity for breaking and connecting, good dynamic stability, flexible combination of programs, novel structure and high protection level. It can be also used as an upgrade and updated product of the low-voltage withdrawable switchgear.

     

    Conditions of Use

    Ambient Temperature: -5℃~+40℃; Average temperature within 24 hours ≤ +35℃.

    Sea Level: ≤ 2000m.

    Installation inclination: ≤ 5°

    No risk of the pollution of corrosive, flammable air or vapor and the place without hazardous explosion

    • Serial Number

      Items

      Unit

      Parameter

      1

      Rated Working Voltage

      V

      ~380

      2

      Rated Frequency

      Hz

      50、60

      3

      Rated Insulation Voltage

      V

      660

      4

      Capacity of the Control Motor

      kW

      0.5~155

      5

      Mechanical Life

      bout

      500

      6

      Rated Current

      Horizontal Busbar

      A

      1600、2500

      Vertical Busbar

      800、1000

      Main Circuit Contacts and Connectors

      100~630

      Auxiliary Circuit Contacts and Connectors

      20

      Supply Circuit Maximum Current

      400

      Power Acceptance Circuit

      1000、1600、2000、2500

      7

      Rated Instantaneous Withstand Current (effective value, 1S)

      kA

      15、30、50

      8

      Rated Peak Withstand Current

      kA

      30、63、105

      9

      Dielectric Strength (1 min)

      V

      2500

       

      Feature

      The main framework is made by the two type structure of 8MF profile steel and part welded. The modular holes by E=20mm is provided on the main structure.

      The function rooms are strictly separated for unit design, bus bar and cables.

      The devices didn't adopt the traditional design of placing the main horizontal bus bar on the top of the switchgear, which make the cable channels can be adopted on the upper and lower part of the cable cabin.

      The dimensions of the switchgear are provided as follows:

      Cabinet Width

      Cabinet Height

      Cabinet Depth

      2200

      400

      800

      1000

      600

      800

      1000

      800

      600

      800

      1000

      1000

      600

      800

      1000

       