- Data Sheet
Product Introduction
The YBD-12KV prefabricated substation with light system is a new type of modular substation, with another name of landscaped style modular substation. YBD-12KV prefabricated substation has two types of solution by ground sunk transformer and advertisement lighting outdoor switchgear system.
The ground sunk transformer includes transformer, HV load switchgear and fuse, which has the compact feature. The transformer is installed into the pit and save the ground space. In special condition, the transformer can be used in a period of water immersed.
The ad lighting outdoor switchgear is combined with ad system and the outdoor switchgear system. This type modular substation is installed on the ground with the advertisements fixed on the both sides, and the outlook can provide the people by excellent visual feeling.
The YBD-12KV prefabricated substation with light system meet the ECO concept of city, with limited floor area and improve the quality of the environment, and well be used for traffic road, residential area, air port, station and highway. Compare with traditional switchgear system, YBD-12KV substation has the advantages of high reliability, energy saving, noise reduced, ECO and high automation.
Model Details
Features
Foundation Base:
The foundation base need to be full sealed with min. 6mm steel plate and pre-folded, to avoid water leakage or dust leakage into the pit. The other alternative solution is to use the concrete, but waterproof treatment must be performed to avoid leakage.
Ground Sunk Transformer:
The shell of transformer is made by stainless steel and full sealed up to IP68, in order to the transformer can be operated while be immersed into the water.
For safety, the HV&LV cable mounting of the inlet and outlet will be waterproof, full insulated and full shield.
The oil for the transformer should be the Cyclopentane oil, since this oil has good heat dissipation.
Advertisement Modular for Outdoor Switchgear
The structure of the substation is the advertisement design, and the two doors can be fully opened with gas spring supports, for good operation and maintenance.
Conditions of Use
Sea Level: ≤ 1000m.
Working Temperature:-25 ℃~+40℃;
Relative Humidity: daily average of not more than 95%; monthly average of not more than 90%
Installation inclination <3 °, no frequent severe vibration shocks.
The ambient air should be free from explosive, flammable, corrosive gases and dust.
Installation
The manufacturer can provide the foundation layout for their modular substation. The customer or user can design the foundation by themselves, but the layout need to be provided for manufacturer.
The lightning conductors need to pre-lay in side or around of the foundation of the modular substation. The ground connection and lightning protection of the transformer can be jointly used as one grounding system. The grounding cables to the foundation platform should be not less than two lines and the grounding resistance should be guaranteed to be less than or equal to 4 Ohm.(R≤4Ω)
For water proof, the gap between the modular substation and the foundation should be sealed with the cement concrete.
Ordering instructions
The information need to be provided by the customer to the manufacturer.
A. Product Model
B. Operation Conditions
C. Transformer Model and Capacity
D. Cable Installation Solution, and Electrical Components’ Model and Parameters
E. Shell Color Code
F. If any other requirements, the clients can provide to manufacturer while place the order.
-
Items
Unit
Parameter
Hight Voltage Components
Rated Frequency
Hz
50/60
Rated Voltage
kV
12
Withstand Voltage of Working Frequency to the ground and phase to phase
kV
42
Withstand Voltage of Thunder Impact to the ground and phase to phase
kV
75
Rated Current
A
630
Rated Short-term Withstand Current
kA
20(2S)
Rated Peak Withstand Current
kA
50
Low Voltage
ComponentsRated Voltage
V
400
Main Circuit Rated Current
A
100-4,000
Rated Short Circuit Withstand Current
kA
50
Rated Peak Withstand Current
kA
105
Transformers
Rated Capacity
kVA
50-2,000
Tapping Range
±2×2.5%
or ±5%
Linked Groups
D,yn11
Noise
dB
≤55
Protection Level
IP33