Product service
Prefabricated substation
YBM26-12
- Description
- Data Sheet
Product Introduction
The YBM26-12 prefabricated substation is a type of modular substation, with another name of ‘European style modular substation’, is a type of compact set of power distribution substation with the components of HV electricity, power transformer and LV electricity, and it is with varied features of high combination, small sizes, removable, safe & reliable operation, easy maintenance and nice shape. This new electrical power distribution substation can be wide range used in the city public distribution, high building, residential quarter, mining, port, oil site, park, car station, air port, subways and high way.
Model Number Details
Features
YBM substation put HV electricity, power transformer and LV electricity into the independent rooms with the solutions of A or B or C. The solution B and C have the advantage of easy installation when the site space is limited. The solution A has convenience of cable assembling than the solution B and C, is well accepted by most customers when no compact of installation space.
YBM series substation has whole sealed structure, and the cabinet body can be made by high strength steel plate, aluminum plate, composite color code steel plate, stainless steel plate and cement board with fiber glass reinforcement. Compared with metal plate, the cement plate with fiber glass reinforcement has been wide-range used for the environment coordination.
The HV switchgear in the modular substation can be selected with five types of air type, pressure air type, vacuum load type, SF6 load type or vacuum circuit breaker. These HV devices have the five type protection functions, and meet the power supply from terminal, ring network and dual power system. The power transformer in the modular substation can be selected with Non-metal & alloy transformer, oil-immersed enclosed transformer or dry power transformer。This type substation also can fit with gas protection and temperature controlling device.
The LV switchgear in modular substation can be selected with the brands of ABB, Schneider and others. The replenish model of the capacitor can be the types of collectively replenish, sub-replenish, completed sub-replenish and Zero-crossing shutting function.
The wire used in modular substation’s input and output is cable. The overhead input cable for HV can be provided for special demand. For convenience of cable installation, a human-hole is designed and provided. For convenience of inner operation, the lights can be turned on and off automatically with the door.
Conditions of Use
Sea Level≤ 1000 meters
Working Temperature -30 ℃ ~ +40 ℃
Relative humidity is less than 90%(+25℃)
No risks of fire, explosion, serious pollution, chemical corrosion and strong vibration installation site。
If user needs higher demands than existing data sheet, user shall contact to the supplier or manufacturer.
Operation and Maintenance
The operation and maintenance of the HV switchgear should be carried according to the HV switchgear installation and operation manual.
The main contactor of air circuit breakers in LV electricity can be partially burnt or carbonized, and increase the resistance, after multiple open and close. The air circuit breakers need the maintenance according to the instruction manual.
The lightning arrester need to be preventive test before the annual storm season.
The cooling system, temperature automatic monitoring system, and the oil temperature or coil temperature in top (dry power transformer), need to be inspected of well working or not.
The operation and maintenance must be performed by the qualified electrical person.
Installation
The manufacturer can provide the foundation layout for their modular substation. The customer or user can design the foundation by themselves, but the layout need to be provided for manufacturer.
The lightning conductors need to pre-lay in side or around of the foundation of the modular substation. The ground connection and lightning protection of the transformer can be jointly used as one grounding system. The grounding cables to the foundation platform should be not less than two lines and the grounding resistance should be guaranteed to be less than or equal to 4 Ohm.(R≤4Ω)
For water proof, the gap between the modular substation and the foundation should be sealed with the cement concrete.
Ordering instructions
The information need to be provided by the customer to the manufacturer.
A. Product Model
B. Operation Conditions
C. Transformer Model and Capacity
D. Cable Installation Solution, and Electrical Components’ Model and Parameters
E. Shell Color Code
F. If any other requirements, the clients can provide to manufacturer while place the order.
-
Items
Unit
Parameter
HV Components
Rated Frequency
Hz
50/60
Rated Voltage
kv
12
Withstand Voltage of Working Frequency, to Ground, or Phase to Phase
kv
42
Withstand Voltage of Thunder Impact Ground, to Ground, or Phase to Phase
kv
75
Rated Current
A
630
Rated Instantaneous Withstand Current
kA
20(2S)
Rated Peak Withstand Current
kA
50
LV Components
Rated Voltage
V
400
Rated Current of Main Circuit
A
100-4000
Rated Instantaneous Withstand Current
kA
50
Rated Peak Withstand Current
kA
105
Transformer
Rated Capacity
kVA
50-2000
Tap Range
±2×2.5%
or±5%
Linked Groups
D,yn11
Noise Level
dB
≤55
Shell Protection Grades
IP33