Integrated
+
  • Integrated

Integrated

Hengxuan Electric is committed to providing customers with research and development, production, sales, and installation (repair, testing) of complete electrical equipment and comprehensive supporting services.

Keywords: High and Low Voltage Complete Sets | Box-type Substation | Power Transformer

  • Description
  • Technical Specifications
  • Simple

    Prefabricated and pre-tested, compact 20 HC container design with no internal wiring required on site, easy to transport

    Efficient

    High-efficiency transformer, increased output, reduced self-consumption, increased output

    Smart

    Real-time monitoring of transformers, low-voltage panels, and RMUs; high-precision sensors for remote control of ACB and MV circuit breakers' low-voltage electrical parameters

    Reliable

    Robust design for harsh environments; optimal cooling design for high availability and easy maintenance; comprehensive testing from components and equipment to solutions

  • Input

    Project Unit   Parameter
    AC Power Supply kVA   6,600/3,300
    Rated Input Voltage V  800 
    Maximum Low Voltage AC Input 37  37 
    Low Voltage Main Switch A/pcs  ACB(2900 A,2pcs)/ACB(2900 A,1 pcs)
    Low Voltage Main Switch A/pcs  MCCB(400 A,24 pcs)/MCCB(400 A,20 pcs)

    Output

    Project Unit Parameter
    Rated Output Voltage kV 10~35kV
    Frequency Hz 50 or 60
    Transformer Type   Oil-immersed
    Transformer Cooling Type   ONAN
    Transformer Tap Changer   ±2×2.5%
    Transformer Oil Type   Mineral Oil
    Transformer Connection Group  Dy11-y11/Dy11
    Transformer Energy Efficiency Level   GB 20052-2020
    RMU Type   SF6/Eco-friendly/Solid
    RMU Transformer Feeder Cabinet   Vacuum Circuit Breaker
    RMU Incoming/Feeder Cabinet   Load Switch
    Auxiliary Transformer kVA Dry type, 5 kVA, Three-phase
    Auxiliary Transformer Output Voltage Vac 400/230 Vac

    Protection

    Project Unit Parameter
    Transformer Body   Oil Temperature, Oil Level, Oil Pressure, Gas
    Medium and Low Voltage Room Protection Level  IP54
    Internal Arc Fault Classification   IAC A 20kA 1s
    Medium Voltage Relay Protection   50/51,50N/51N
    Low Voltage Overvoltage Protection   Type I+II

    General

    Project Unit Parameter
    Dimensions (W×H×D)   6,058×2,896×2,438 mm (ISO 20’ Container)
    Weight   <22t<15 t
    Operating Temperature Range   -25℃~60℃
    Relative Humidity   0%~95%
    Altitude  1000m
    MV-LV AC Connection   No On-site Connection Required
    Low and Medium Voltage Room Cooling   Air Conditioning
    Communication

Application Industries

Message

If you have any needs, please feel free to contact us.

Submit Now
Business License