Product service
Combined substation
YBM-40.5
- Description
- Data Sheet
Product Introduction
The YBM-40.5 prefabricated substation is one of the series products designed and manufactured to meet the needs of development of State Grid and the wind power industry, which is suitable to the system of the three-phase AC system with the rated voltage 35/10kV, 6kV, 0.69 kV, 0.4kV with the rated frequency of 50HZ , for the electric power acceptance and distribution. The YBM-40.5 has the various advantages of short construction period, save space, competed set, limited investment, removable, easy installation and operation, high reliability and widely used in the construction of city, town, factory, mining, oil fields, port and the wind power industry, also comply to the site of big construction.
Features
YBM-40.5 prefabricated substation is a high voltage substation system with the 35kV HV electricity, 35/10(6)kV power transformer, 10kV switchgear,0.68(0.4kV) low voltage switchgear, DC battery system and relay protection system. The YBM-40.5 prefabricated substation has two types design by integrated and split. For the split type, the transformer is outdoor installed, and build a safety space through certain protection intervals, and connected by the overhead buses and cables between the transformer and the two switchgears
The shell of YBM-40.5 prefabricated substation is made of high quality steel plates with the surfaces anti-corrosion and spray coating treatment. The alternative panel sheet is made by the color steel sandwich boards with insulation. If final using site is the wind power system, the concrete plate with fiber glass reinforcement could be proposed. The cooling system of the power transformer is made by the natural wind ventilation system and the forced ventilations. The controlling of the temperature and the humidity of the rooms for HV,MV and LV is made by the air conditioners and anti-gel devices. All the rooms and accesses are equipped with lights for easy operation and observation.
The HV side of 35kV in YBM-40.5 prefabricated substation can use the XGN-40.5 fixed type prefabricated switchgear or KYN-40.5 armoured removable switchgear or ABB GIS-ZX140.5kV switchgear.
12KV Switchgear Room
KYN28-12-type Armored Removable Switchgear
HXGN-12-type Ring Net Switchgear
HXGN-12-type Fixed Switchgear
0.69KV LV Equipment Room (wind power generation)
The 0.69kV LV electricity is used in YBM-40.5 prefabricated substation, and mainly suitable for wind power generation. The switchgear models could be GCK, GCS, MNS, and GGD, etc.
Relay Protection Room
In the relay protection room, the panels of AC, DC, signal and motion controlling(RTU), carrier wave or fiber-optic terminal.
Note: According to the user's requirements, the substation can adopt the conventional relay protection or the integrated PC automatic system.
Foundation
The foundation of the prefabricated substation is the concrete foundation with steel reinforcements on outdoor ground. The transformer, 40.5kV switchgear room and 12kV switchgear room are all separated units for flexible transportation, and make combination at site.
The power supply is realized with overhead buses or cables. The customers can make choice according to the project requirements, and can specify the details while ordering.
Ordering instructions
The information need to be provided by the customer to the manufacturer.
A. Product Model
B. Operation Conditions
C. Transformer Model and Capacity
D. Cable Installation Solution, and Electrical Components’ Model and Parameters
E. Shell Color Code
F. If any other requirements, the clients can provide to manufacturer while place the order.
-
Items
Unit
Parameter
HV Components
Rated Frequency
Hz
50/60
Rated Voltage
kV
35
Withstand Voltage of Working Frequency, to Ground and Phase to Phase
kV
95
Withstand Voltage of Thunder Impact ,to Ground and Phase to Phase
kV
185
Rated Current
A
630
Rated Instantaneous Withstand Current
kA
20(2S)
Rated Peak Withstand Current
kA
50
MV Components
Rated Voltage
kA
12
Withstand Voltage of Working Frequency Ground, or Phase to Phase
kV
42
Withstand Voltage of Thunder Impact Ground, or Phase to Phase
kV
75
Rated Current
kV
630
Rated Instantaneous Withstand Current
A
20(2S)
Rated Peak Withstand Current
kA
50
LV Components
Rated Voltage
kA
690
Main Circuit Rated Current
A
100-3200
Rated Instantaneous Withstand Current
kA
50(1S)
Rated Peak Withstand Current
kA
105
Transformer
Rated Capacity
kVA
50-1600
Tap Range
±2×2.5%
or±5%
Linked Groups
D,yn11
Noise Level
dB
≤55