JBM series are containerized substation, and the substation shell is stand10’、 20’、40‘ container dimensions and have very compact steel container structure. JMB series containerized substation can provide the different custom design of side wall with standard container lock or panic lock, ventilation window with cover or without cover, internal partition design with or without insulation, and different internal packing solution.
Furthermore, the lighting system, client logo label and different inner insulation panel could be provided as options.
JBM series substation can be delivered as standard dry container for the international road, train and ocean transportation, and the CSC test and certificate could be provided if customer has the requirement.
-
Dimensions and weight
Commodity
Width(mm)
Height(mm)
JBM-10
2438
2591
JBM-20
2438
2591
JBM-40 2438 2591/2896 Depth(mm) Weight(Kg) JBM-10 2991 2500 JBM-20 6058 5500 JBM-40 12192 6500 DATA SHEET
Items Unit Parameter Rated Voltage Primary kV
10 Secondary 0.4 Maximum Working Temperature kV 12 Rated Frequency HZ 50 Rated Capacity kVA 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1,000, 1,250, 1,600 1 Minute Working Frequency Withstanding Voltage kV 42(Exclude transformer)
35(Include transformer)
BIL Impulse Withstanding Voltage kV 75 Cooling Type Oil-immersed self-cooled No-load tap changer kV ±2×2.5% Ambient Temperature ℃ -45~+40 The Allowable Temperature Rise of the Top Layer of the Transformer k ≤55 Low-voltage Transformer Winding Temperature Rise k ≤65 High-voltage Transformer Winding Temperature Rise k ≤65 Noise Level dB ≤55 Protection Level IP 33 Items Unit Parameter Rated Voltage Primary kV
20 Secondary 0.4 Maximum Working Temperature kV 24 Rated Frequency HZ 50 Rated Capacity kVA 100, 125, 160, 200, 250, 315, 400, 500, 630, 800, 1,000, 1,250, 1,600 1 Minute Working Frequency Withstanding Voltage kV 55 BIL Impulse Withstanding Voltage kV 125 Cooling Type Oil-immersed self-cooled No-load tap changer kV ±2×2.5% Ambient Temperature ℃ -45~+40 The Allowable Temperature Rise of the Top Layer of the Transformer k ≤55 Low-voltage Transformer Winding Temperature Rise k ≤65 High-voltage Transformer Winding Temperature Rise k ≤65 Noise Level dB ≤55 Protection Level IP 33