Gutiergear-12

固体绝缘高压柜Gutiergear-12

固体绝缘高压柜Gutiergear-12

  • Description
  • Data Sheet
  • FEATURES

    Miniaturization:min. width 450mm, min. height 1,700mm.

    Stationary type:The cabinet is made up of two units with fixed setting solution.

    Solid insulation:The vacuum arc-extinguishing chamber can reduce parts, environmental and stable.

    Modularization:Replaced fast without influencing the feature of products;Secondary control parts easy to maintain;Convenient and humanized operating handle

     

    Intelligent:Combination of breaker and switch:

    Switch:Load switch 630A/25kA;Breaker cabinet 630A/25kA;Load switch + fuse cabinet 125A/31.5kA

    Scheme for whole series:Up isolation and up earthing;Down isolation and down earthing

     

    Program Code:

    L: Cable cabinet

    T: Combination Cabinet

    V: Circuit breaker Cabinet

    D: Cable cabinet without switch

    M: Metering Cabinet

    PT: Potential Transformer Cabinet without switch

    KPT: Potential Transformer Cabinet with switch

     

    SWITCH CHAMBER

    The compact switch cabinet is made up of sealed box and solid insulator.

    No condensation or a reduction of insulating ability caused by erosion because it is isolated from the outer

     

    USE CONDITIONS

    No disasters or risks of fire, explosion, pollution, chemical corrosion and vibration etc.

    Temperature: +50℃~ -40℃

    Sea Level: ≤4,000m

    Relative Humidity: ≤95%, 2.2kpa (24 hours) ≤90%, 1.8kpa (1 month)

    Earth Quake: ≤8

     

    OVERVIEW OF THE GUTIERGEAR

    Gutiergear cabinet is made by high strength galvanized steel plate and high strength hardware. The cabinet with integral design has high mechanical

    strength, precision and resistance to corrosion and oxidation with nice appearance. The meter chamber and cabinet body are in whole assembly structure. The switchgear can be removed out without dismantling the secondary connection in replacement, which reduces much workload of mainte-nance. Door panel of breaker chamber is in the pattern of fixed setting. The secondary cable channel is on both sides of front switchgear.

    • Common parameters of switchgear

      No

      Commodity Name

       

      Unit

      Parameter

      1

      Type of arc-extinguishing

       

       

      Vacuum

      2

      Rated Voltage

       

      kV

      12

      24

      3

      Rated Frequency

       

      Hz

      50/60

      4

      Rated Current

       

      A

      630,1250

      5

      Temperature Rise Test

       

       

      1.1lr

      6

      1min Rate Power-frequency Withstand Voltage

      Phase to phase and phase to ground

      kV

      42

      65

      Fracture

      kV

      48

      79

      7

      Peak Value of Rated Lightning Impulse Withstand Voltage(1.2/50Ous)

      Phase to phase and phase to ground

      kV

      75

      125

      Fracture

      kV

      85

      145

      8

      Subsidiary and Control Loop Short-time Power-frequency

       

      kV

      2

      9

      Rated Short-circuit Breaking Current

       

      kA

      25

      10

      Rated Short-time Withstand Current/Duration

      Main circuit and

      kA/s

      25/4

      Earthing circuit

       

      21.7/4

      11

      Rated Peak Value Withstand Current

       

      kA

      63

      12

      Rated Short-circuit Making Current

       

      kA

      63

      13

      Rated Active Load Current

       

      A

      630

      12

      Power Supply

      Control circuit

       

      DC48/110

      Subsidiary circuit

      V

      AC220

      15

      Partial Discharge Capacity (measured value under 1.2Ur)

       

      pC

      ≤20

      16

      Protection Level

      Shell of switchgear

       

      IP4X

      Main circuit and sold insulater

       

      IP67

      17

      Service Life

       

      Y

      40

       

      Load Switch

      No

      Commodity Name

       

      Unit

      Parameter

      1

      Type

       

       

      SICL

      2

      Type of arc-extinguishing

       

       

      Vacuum

      3

      Rated Current

       

      A

      630

      4

      Rated Short-time Withstand Current/Duration

       

      kA/s

      25/4

      5

      Rated Peak Value Withstand Current

       

      kA

      63

      6

      Rated Short-circuit Making Current

       

      kA

      63

      7

      Rated Short-circuit Making Frequency

       

      Times

      3

      8

      Rated Active Load Breaking Current

       

      A

      630

      9

      Rated Cable Charging Breaking Current

       

      A

      10

      10

      Average Speed of Switch on and off

      Speed of Switch off

      kA/s

      1.1±0.2

      Speed of Switch on

      0.8±0.2

      11

      Bounce Time of Switch on

       

      m/s

      ≤2

      12

      Rebounded Amplification of Switch off Contact

       

      mm

      ≤3

      13

      Time of Switch on

       

      ms

      ≤30-70

      14

      Time of Switch off

       

      ms

      ≤20-50

      15

      Non=synchronous Three-phase

       

      ms

      ≤2

      16

      Resistance of Main Circuit

       

      μΩ

      ≤120

      17

      Mechanical Life

       

      Times

      10000

       

       

      Breaker

      No

      Commodity Name

       

      Unit

      Parameter

      1

      Type of Break

       

       

      SICB

      2

      Type of arc-extinguishing

       

       

      Vacuum

      3

      Rated Current

       

      A

      630,1250

      4

      Rated Short-Circuit Breaking Current

      Effecieve value of alternating component

      kA

      25

      On-off frequency

      Times

      30

      5

      Rated Operating Sequence

       

       

      O-0.3s-CO-180s-CO

      6

      Rate Short-time Withstand Current/Duration

       

      kA/S

      25/4

      7

      Rated Peak Value Withstand Current

       

      kA

      63

      8

      Rated Short-circuit Making Current

       

      kA

      63

      9

      Average Speed of Switch on and off

      Speed of Switch off

      m/s

      1.1±0.2

      Speed of Switch on

      m/s

      0.8±0.2

      10

      Bounce Time of Switch on

       

      m/s

      ≤2

      11

      Rebounded Amplification of Switch off Contact

       

      mm

      ≤2

      12

      Time of Switch on

       

      ms

      ≤30-70

      13

      Time of Switch off

       

      ms

      ≤20-50

      14

      Non=synchronous Three-phase

       

      ms

      ≤2

      15

      Different Phase Earthing Fault Breaking Test

      Test Current

      kA

      21.7

      Test Voltage

      kV

      12

      16

      Capacitive Current Breaking Test

      Test Current

      A

      25

      Test Voltage

      kV

      12

      17

      Resistance of Main Circuit

       

      μΩ

      ≤120

      18

      Mechanical Life

       

      Times

      10000

       

      Isolating Switch

      No

      Commodity Name

       

      Unit

      Parameter

      1

      Rated Current

       

      A

      630,1250

      2

      Resistance of Main Circuit

       

      μΩ

      ≤20

      3

      Rated Short-time Withstand Current/Duration

       

      kA/S

      25/4

      4

      Rated Peak Value Withstand Current

       

      kA

      63

      5

      Mechanical Life

       

      Times

      3000

       

       

Add: No.6 Kaiyuan Rd, Hai’an city, Jiangsu Province, China, 226600